CALCULATION OF THE DIMENSIONS AND DYNAMICS OF THE FORMATION OF LOCAL EXPLOSION-HAZARDOUS ZONES IN PROPAGATION AND COMBUSTION OF HYDROGEN WITHIN A BUILDING
S. V. Puzach UDC 614.841.4-536.242 On the basis of numerical calculations by a three-dimensional mathematical model, the author revealed some special features of heat and mass transfer within a building in the inflow of hydrogen at the floor level and subsequent detonation combustion of a local hydrogen-air mixture upon its ignition on the ceiling surface. By generalizing calculation results, the author obtained formulas for determining the height of a local explosion-hazardous zone which is formed above the source of hydrogen inflow. It is shown that in detonation combustion, local explosion- and fire-hazardous zones near the source of ignition can be destroyed and shifted to the lower and upper parts of the building toward the wall which is opposite to the opening. JEPTER7492020008 JEPTER749208